17
2.5kVA Inverter Generator VF2200IG
!
WARNING
Grounding is not required when the generator
is used as a portable power source. Below
grounding method is only needed by a qualified
electrician if connecting through your building’s
electrical system.
If the generator is not grounded through your building’s electrical system, follow the
procedure below fig 1. This procedure can only be carried out by a licensed electrician.
1. Drive a 20mm or 25mm (¾” or 1”) copper pipe or rod into the ground close to the
generator. The pipe/rod must penetrate moist earth – the depth required will be
dictated by local soil conditions.
2. Connect an approved ground clamp to the pipe.
3. Run a 10 gauge wire from the clamp to the generator grounding post located on the
rear of the generator head.
4. Do not connect the generator grounding post to a water pipe or a ground used by a
radio system.
fig 1
Extension cords
Extension cords may be used to power devices that are located at a distance from the
generator. However, use only Australian approved outdoor - rated, grounded extension
cords. Locate the generator in a convenient place and where possible avoid long
extension leads and possible damage to leads by pedestrians or vehicular traffic.
ECO
OFF
OFF
ON
ON
12V DC 8A
PARALLEL OUTLETS
TYPE - C
QC 3.0
AC 240V
OUTPUT
OVERLOAD
Grounding Post
Control Panel
Ground
Copper Pipe Rod
10 Ga. Wire