background image

BLOCK DIAGRAM OF 165EL

INSTALLATION
Example of attaching to actuator

Example 1. 

Case of directly attaching to diaphragm valve.

Example 2.  

Case of using a bracket.

Connection with Feedback Lever

Attach in the position that the valve stem and lever form a right angle when the
input signal is 50%. Attach to the position that the runout angle is within the range
of 10 to 30°.

INSTALLATION cont.
Direct Action & Reverse Action

Attach the cam in the procedure of loosening the hexagonal nut with flange first,
setting the actuator to the starting position and then setting the cam reference line
and the bearing contact point of span adjusting arm unit to the same position. Do
not apply the supply pressure when attaching the cam as otherwise it is very dan-
gerous. When the positioner is shipped out, the cam is tentatively tightened to the
shaft. Be sure to firmly lock the cam to the lock nut [tightening torque 17.7 to 22.1
in-lbs (2.0 to 2.5 NM)].

AIR PIPING CONNECTION

Fully  purge  the  pipe  to  remove  foreign  matter.  Use  a  clean  supply  air  fully
removed of humidity and dust. Use a Series AFR filter regulator to keep supply
air pressure constant.

Summary of Contents for PRECISOR II 165EL Series

Page 1: ...rect action or vice versa Easy feedback connection Fast and accurate response Low air consumption Designed as multi port type for air tubing Easy to install air tubing connection in any direction Designed as block build structure for maintenance and repair STRUCTURE Series 165EL PRECISOR II Electro Pneumatic Linear Positioner Specifications Installation and Operating Instructions Bulletin F 90 TM ...

Page 2: ... hexagonal nut with flange first setting the actuator to the starting position and then setting the cam reference line and the bearing contact point of span adjusting arm unit to the same position Do not apply the supply pressure when attaching the cam as otherwise it is very dan gerous When the positioner is shipped out the cam is tentatively tightened to the shaft Be sure to firmly lock the cam ...

Page 3: ...t of turning varies by actuators Do not loosen the stopper screw at this time since it is set to avoid the screw coming off Ps Supply Pressure Low Pressure Balance 0 4 0 5 Ps Med Pressure Balance 0 5 Ps High Pressure Balance 0 9 1 0 Ps Normal Balanced Point Balanced Point Balanced Point Input Pressure Output Pressure Output Pressure Output Pressure MAINTENANCE If the supply air is fouled the posit...

Page 4: ...ng contact or search of Flapper Clogged fixed orifice Clogged nozzle Off positioned stabilizer spring Too low of actuator volume Clogged fixed orifice Wrong connection of OUT1 and OUT2 tube Wrong setting of feed back lever Wrong Zero Span Adjustment Supply pressure is unstable Wrong setting of Seat Adjuster Loose connection of actuator and positioner Cam Shaft is worn out What To Do Input or incre...

Reviews: