TROUBLESHOOTING

Condition

Not operating with Input
Signal applied

    OUT1 pressure raised, 
does not come down

Output pressure is oper-
ated by A/M switch only
Hunting occurs

Actuator is operated by
On/Off only
Linearity is not good

Hysteresis is not good

Cause

Too low or no supply air
Loose connection
Wrong wiring for (+) and (-)
Short or open circuit of terminal
motor
Clogged nozzle
Loose or wrong setting of 
feedback lever
Leakage of A/M switch
Wrong contact or search of
Flapper
Clogged fixed orifice
Clogged nozzle

Off-positioned stabilizer spring
Too low of actuator volume
Clogged fixed orifice
Wrong connection of 
OUT1 and OUT2 tube
Wrong setting of feed-
back lever
Wrong Zero, Span Adjustment

Supply pressure is unstable
Wrong setting of Seat 
Adjuster
Loose connection of actuator
and positioner
Cam Shaft is worn out

What To Do

Input or increase supply air 
Tighten set screw of terminal
Connect wiring (+) and (-)
Replace Motor Unit

Replace Motor Unit
Correct setting and tighten

Tighten or replace A/M switch
Replace Motor Unit

Clean or replace fixed orifice
Clean nozzle or 
replace Motor Unit
Insert stabilizer spring
Insert orifice
Clean or replace fixed orifice
Correct position of tube

Readjust setting of 
feedback lever
Readjustment of Zero, Span
Adjustment
Replace regulator
Readjust Seat Adjuster

Tighten connection

Replace Cam Shaft

Summary of Contents for PRECISOR II 165EL Series

Page 1: ...rect action or vice versa Easy feedback connection Fast and accurate response Low air consumption Designed as multi port type for air tubing Easy to install air tubing connection in any direction Designed as block build structure for maintenance and repair STRUCTURE Series 165EL PRECISOR II Electro Pneumatic Linear Positioner Specifications Installation and Operating Instructions Bulletin F 90 TM ...

Page 2: ... hexagonal nut with flange first setting the actuator to the starting position and then setting the cam reference line and the bearing contact point of span adjusting arm unit to the same position Do not apply the supply pressure when attaching the cam as otherwise it is very dan gerous When the positioner is shipped out the cam is tentatively tightened to the shaft Be sure to firmly lock the cam ...

Page 3: ...t of turning varies by actuators Do not loosen the stopper screw at this time since it is set to avoid the screw coming off Ps Supply Pressure Low Pressure Balance 0 4 0 5 Ps Med Pressure Balance 0 5 Ps High Pressure Balance 0 9 1 0 Ps Normal Balanced Point Balanced Point Balanced Point Input Pressure Output Pressure Output Pressure Output Pressure MAINTENANCE If the supply air is fouled the posit...

Page 4: ...ng contact or search of Flapper Clogged fixed orifice Clogged nozzle Off positioned stabilizer spring Too low of actuator volume Clogged fixed orifice Wrong connection of OUT1 and OUT2 tube Wrong setting of feed back lever Wrong Zero Span Adjustment Supply pressure is unstable Wrong setting of Seat Adjuster Loose connection of actuator and positioner Cam Shaft is worn out What To Do Input or incre...

Reviews: