Page 42 of 48
PAM-199-P
5.28
MIN (Overlap compensation)
5.29
MAX (Output scaling)
5.30
TRIGGER (Threshold value of MIN function)
Command
Parameters
Unit
Group
FUNCTION
MIN:I
X
MAX:I
X
TRIGGER X
i= A|B
x= 0… 6000
x= 5000… 10000
x= 0… 3000
-
0.01%
0.01%
0.01%
STD
195
197
The output signal is adapted to the valve by these commands. With the MAX value the output signal (the maxi-
mum valve current) will be defined. With the MIN value the overlap (dead band of the valve) will be compen-
sated. Via the TRIGGER the activation point of the MIN function is set and so a non-sensitive range around
the zero-point
2
can be specified.
CAUTION
: If the MIN value is set too high, it influences the minimal velocity, which cannot be
adjusted any longer.
2
This dead band is necessary, in order to avoid unrequested activations caused by small variations of the input signal. If
this module is used in a position controls, the TRIGGER value should be reduced (typical
: 1…10).
MAX:A
MIN:A
MIN:B
MAX:B
Input
O
u
tp
u
t
TRIGGER