Page 26 of 34
SCU-138-P-2230
5.5.4
SIGNAL:U (Output polarity)
Command
Parameter
Unit
Group
SIGNAL:U X
x= 1S+|1S-|2S+|2S-
-
EXP
This command is used to define the type of the controller and accordingly the output signal and its polarity.
Selectable are one solenoid or two solenoid control. Furthermore the direction of the output signal can be
switched. Using applications with one solenoid it means an inverted characteristic curve. If two solenoids are
used it effects the switching of the solenoids.
1S+: One solenoid standard
o
U = 0… 100% -> IA = 0… 100%
1S-: One solenoid inverted
o
U = 0… 100% -> IA = 100… 0%
2S+: Two solenoids standard
o
PIN 6 not set -> Controlling IA,
0… 100%
o
PIN 6 set
-> Controlling IB,
0… 100%
2S-: Two solenoids switched
o
PIN 6 not set -> Controlling IA, 10
0… 0%
o
PIN 6 set
-> Controlling IB, 10
0… 0%
CAUTION:
Controlling the second solenoid is realized via the digital input at PIN 6. If a two
solenoid controlling is chosen here, the START signal for the controller is not longer available.
With setting ENABLE the controller is imeadiatelly activated.