 Operating manual 

 

 

 

- 8 - 

5.2  

Electrical installation 

The terminals configuration are shown in Figure 01. 

 

 

 

Figure 01

: Input connections and power supply 

 

 

 

 

Figure 02

:

 

Thermocouple, Pt100 and 50 mV signal connection 

 

 

 

 

 

Figure 03

: Current (mA) and Voltage (V) signal connection 

 

This indicator offers an auxiliary 24 VDC +/-15% at 50 mA power supply which is typically applied to 
power up two wire 4 to 20 mA field transmitters. The 

Figure 04 

presents the wiring for this 

application. 

 

 

 

 

Figure 04: 

Auxiliary 24 VDC usage example 

 

 

5.3 

 Recommendations for the installation 

 

To minimize the pick-up of electrical noise, the low voltage DC connections and the sensor 
input wiring should be routed away from high-current power conductors. If this is impractical, 
use shielded cables. In general, keep cable lengths to a minimum. 

 

The input signal conductors shall be positioned throughout the factory separate from the output 
and the power supply conductors, in grounded conduits if possible. 

 

The power supply of the electronic instruments shall come from a proper source for the 
instrumentation network. 

 

It is recommended to use RC FILTERS (0,1uF in series with 100 ohms) to suppress the noise 
generated by contactors coils, solenoids, etc. 

 
 
 

Summary of Contents for DA9602

Page 1: ...ndorff Prozesstechnik GmbH Co KG Industriestra e 7 D 65366 Geisenheim Tel 49 6722 9965 20 Fax 78 All Information without warranty errors and changes reserved Universal display DA9602 Operating manual...

Page 2: ...on 6 4 10 F1 and F2 function keys 6 4 11 Overflow alarm 7 4 12 Minimum and maximum 7 4 13 24 VDC auxiliary voltage source 7 4 14 Interface 7 5 Installation 7 5 1 Mechanically installation 7 5 2 Electr...

Page 3: ...vent dangerous situations on machinery and installations Machinery and intallations must be designed that fault conditions can not lead to harmful situations to operating personnel e g by independent...

Page 4: ...mocouple K Range 150 C to 1370 C 238 F to 2498 F Thermocouple T Range 160 C to 400 C 256 F to 752 F Thermocouple N Range 270 C to 1300 C 454 F to 2372 F Thermocouple R Range 50 C to 1760 C 58 F to 320...

Page 5: ...oint defined by ALrF SPA1 using alarm 1 as an example ALrF PV ALrF SPA1 ALrF PV ALrF SPA1 SPA1 positive SPA1 negative Alarm of the Maximum Differential Value It triggers when the value of the PV is ab...

Page 6: ...ory and can also be presented at the indicator display by choosing TOTAL screen which is identified by the symbol TOT This symbol is always presented when the TOTAL is being presented The TOTAL value...

Page 7: ...W identify if the part being displayed is the SP most significant part HIGH or the least significant part LOW The totalization alarm SP is defined through the values SPA1 and SPA2 This two parameters...

Page 8: ...e 5 3 Recommendations for the installation To minimize the pick up of electrical noise the low voltage DC connections and the sensor input wiring should be routed away from high current power conducto...

Page 9: ...cording to the desired behavior The user shall understand the importance of each parameter and determine a valid condition or a valid value for each one of them The configuration parameters are groupe...

Page 10: ...SP decimal point SetPoint Alarm Alarm SP Value that defines the point of activation of the alarm outputs For the alarms programmed with the functions of the type Band and Differential these parameter...

Page 11: ...indication range when the input types of 0 20 mA 4 20 mA 0 50 mV 0 5 V and 0 10 V are used Defines the function to be executed by F1 and F2 keys No associated function Executes Batch Function Addition...

Page 12: ...p the Level of Protection See Table 03 Frequency Frequency of the local electrical network Serial number 4 most significant digits Serial number 4 least significant digits 8 6 Password protection The...

Page 13: ...in the event of it being forgotten The Master Password doesn t grant access to all parameters only to the Password Change parameter After defining the new password the protected parameters may be acce...

Page 14: ...0 mV 10 M 0 to 5 V 0 to10 V 500 k 4 to 20 mA 100 Measuring of the Pt100 3 wire type 0 00385 with compensation of the cable length max 50 meters excitation current of 0 170 mA OUTPUT Output ALARM1 Rela...

Page 15: ...nical content within this document can be modified without notice The content of this document is content of a recurring audit In losses due to fire earthquake interventions by third or other accident...

Reviews: