UR3274U - User manual
97
1009
Heating output percentage (0-10000) RO
0
1010
Cooling output percentage (0-10000) RO
0
1011
Alarms status (0=none, 1=active)
Bit0 = Alarm 1
Bit1 = Alarm 2
RO
0
1012
Manual reset:
write 0 to reset all the alarms.
In reading
(0=not resettable, 1=resettable):
Bit0 = Alarm 1
Bit1 = Alarm 2
WO 0
1013
Error flags
Bit0 = Eeprom writing error
Bit1 = Eeprom reading error
Bit2 = Cold junction error
Bit3 = Process error (sensor)
Bit4 = Generic error
Bit5 = Hardware error
Bit6 = Master off-line
Bit7 = Missing calibration data
RO
0
1014
Cold junction temperature
(tenths of degree)
RO
-
1015
Start/Stop
0=controller in STOP
1=controller in START
R/W 0
1016
Lock conversion ON/OFF
0=Lock conversion off
1=Lock conversion on
R/W 0
1017
Tuning ON/OFF
0=Tuning off
1=Tuning on
R/W 0
1018
Automatic/manual selection
0=automatic 1=manual
R/W 0
1019
OFF LINE
*
time (milliseconds)
R/W 0
1100
Process visualized (decimal as display) RO
-
1101
Visualized Setpoint 1 (decimal as
display)
R/W EEPROM