Operation
7.11 Alarms and Shutdown Conditions
68
Operator’s Manual | LTV 4L/6L | 5100065071 | 02/2023 | [en-US]
wc_gr012357
Displays the available voltage of the battery.
wc_gr012360
Displays the maintenance interval as well as the time remaining until main-
tenance is required.
Each parameter is displayed on a separate screen:
• Oil change
• Air filter
• Fuel filter
7.11
Alarms and Shutdown Conditions
Background
The machine controller monitors variables of engine and machine function.
The machine controller has two types of alarms: warning alarms and shut-
down alarms.
wc_gr012354
a
b
c
d
e
1
2
3
4
5
Fig. 39: Warning alarms
Warning alarms
Warnings are non-critical alarm conditions that do not affect the operation of
the generator system. They serve to draw the operator’s attention to an un-
desirable condition. Warning alarms are self-resetting when the fault condi-
tion is removed.
Warning alarms include:
• Generator over-frequency
(1)
• Generator under-frequency
(2)
• Time to maintenance—oil
(3)
• Time to maintenance—air filter
(4)
• Time to maintenance—fuel filter
(5)
During a warning alarm condition, the LCD panel displays the type of warn-
ing alarm. The machine is not shut down.