Operation
LTV
5.11
Starting, Operating, Stopping the Machine—DeepSea
Prerequisites
■
Before starting checks completed. See topic
Before Starting.
■
Electrical cables in good condition with no cuts or abrasions in the insulation.
■
Circuit breakers
(a, b, c and d, h for 8K)
are in the OFF position.
■
All loads are disconnected from the machine.
NOTICES
■
Do not use evaporative starting fluids (for example, ether) to start the engine.
■
Do not start the engine under load.
Procedure
Follow the procedure below to manually start the machine.
1. Press the START switch
(f)
.
This initiates the pre-heat timer, energizes the fuel
solenoid, and energizes the starter motor.
2. The engine will crank for 10 seconds, and then rest for 10 seconds. If the engine
does not start immediately, the cycle will repeat three (3) times.
3. If the engine does not start after three attempts, the starting sequence will be
terminated and the Overcrank shutdown indicator
(g)
will light.
4. When the engine starts, the starter motor is disengaged.
Note: After the starter motor has disengaged, the Safety On Timer is activated.
This timer is pre-set for a 12 second delay and allows oil pressure, high engine
temperature, underspeed, and charge failure to stabilize without triggering the
fault.
5. If a fault occurs after the 12-second delay, see section
Meanings of Genset
Controller Indicator Lights.
6. Allow engine to warm up before operating lights.
This procedure continues on the next page.