background image

INTERCEPTORS

 

4

 

Wade

 

Drains

 ‐ 

11910

 

CR492,

 

Tyler,

 

TX,

 

75706

 ‐ 

Phone:

 

800

638

9537

 

Fax:

 

888

879

9233

 ‐ 

www.wadedrains.com

 

3

29

17

 

 

INSTALLATION 

Install the interceptor as close as practical to the fixture(s) being served. Avoid installations where long runs of pipe 
(exceeding 25’) are necessary to reach the interceptor. This precaution will preclude the possibility of grease becoming 
congealed in the pipe before it reaches the interceptor. 

The unit may be placed on the floor, partially recessed in the floor, recessed with the top flush with the floor or encased 
below the floor in an appropriate housing to accommodate piping and structural considerations. Whatever the installation 
method, anticipate sufficient clearance to remove the cover and baffle for cleaning. Verify that no obstructions will be 
placed over the interceptor after installation. A minimum clearance equal the overall height of the interceptor (excluding 
any extension) is recommended. 

Do not install the grease interceptor in a waste line from a garbage grinder. 

Garbage grinder waste must bypass the interceptor because the rapid accumulation of solid matter will significantly 
reduce the rated efficiency of the interceptor. In an application where solids will be present, a solids interceptor should 
be used. 

A separate grease interceptor is recommended for each commercial dishwasher. 

The size is determined by the discharge rate of the dishwasher as stated by the manufacturer. 

Placement of a grease interceptor in a high traffic area is an important concern. If the unit is to be installed flush with the 
floor, it is necessary to load rate the interceptor cover. The standard Wade interceptor is designed for pedestrian and 
light traffic only. If heavy loads are anticipated, the interceptor must be specified with an appropriate reinforced cover. An 
extension is frequently used to increase the rough-in dimension from the inlet/outlet centerline to the finished floor. The 
extension anchor flange is not adequate to support the entire interceptor. For installations at flush-with-floor 

level, the interceptor chamber must rest on solid ground or a concrete pad. For upper floor installations, (suspended 
above the lower floor ceiling), the interceptor must be independently supported on hangers suitable to carry the entire 
weight. 

A single interceptor serving multiple fixtures is recommended only where the fixtures are located close together. In these 
installations, each fixture should be individually trapped and vented. 

Summary of Contents for 5100

Page 1: ... prevent odor from escaping An air relief is provided to eliminate siphonage and each unit is furnished with a flow control device to insure it will perform to its rated capacity OPERATION Waste water draining to the interceptor passes through the flow control device which regulates the velocity to a controlled rate As water enters the interceptor the baffle arrangement reduces turbulence to allow...

Page 2: ...17 1 4 14 23 1 4 4 1 2 108 0 35 70 28 6 22 1 2 28 3 4 20 17 1 4 18 25 3 4 4 1 2 129 0 50 100 37 4 22 1 2 30 24 21 1 4 18 27 1 4 4 1 2 151 0 75 150 57 1 23 3 8 34 5 8 30 5 8 27 7 8 17 1 2 31 7 8 5 7 8 156 0 100 200 106 2 27 5 8 41 3 8 35 5 8 32 7 8 22 38 5 8 5 5 8 172 0 Wt Lbs 4 8 4 4 10 1 2 18 13 10 25 7 15 1 4 3 1 2 40 0 Size GPM Suffix Op ons HD Heavy Duty Cover 24 Anchor Flange 26 Anchor Flange w...

Page 3: ...INTERCEPTORS 3 Wade Drains 11910 CR492 Tyler TX 75706 Phone 800 638 9537 Fax 888 879 9233 www wadedrains com 3 29 17 5100 Grease Interceptor ...

Page 4: ...duce the rated efficiency of the interceptor In an application where solids will be present a solids interceptor should be used A separate grease interceptor is recommended for each commercial dishwasher The size is determined by the discharge rate of the dishwasher as stated by the manufacturer Placement of a grease interceptor in a high traffic area is an important concern If the unit is to be i...

Page 5: ... single flow control may be used The supplied flow control device must be properly vented to permit air to mix with the fluid entering the interceptor Air facilitates the separation and more Importantly is necessary to maintain optimum pressure thereby maintaining the proper operating level within the interceptor chamber The flow control air intake may terminate under the sink drain board as high ...

Page 6: ... time thus allowing these particles to pass through the interceptor Increasing the size of the interceptor will allow longer retention rates and improve the efficiency Flow Capacity If maximum recommended flow rates are exceeded the efficiency of the interceptor will be decreased Either install additional flow controls devices at all sources of flow or install a larger interceptor Specific Gravity...

Page 7: ...r the unit has been in operation for several weeks A logical cleaning schedule is normally determined by checking the unit after a normal shift or following a period of peak usage Grease removal intervals may vary from once a week to once in several weeks Never clean an interceptor during a time when customers are present as the offensive odors may develop inside the interceptor Cleaning can easil...

Page 8: ... position 3 Remove the bronze plug from the cover and insert the hose fitting and flexible draw off hose tightening the hose fitting securely Place the end of the hose into a container suitable for disposal 4 Turn the hot water supply back on back on and allow the water pressure to steadily force the liquefied grease through the hose Caution The liquid grease may be hot when exiting the draw off h...

Page 9: ...xtension is specified by expanding the H dimension on the interceptor The H dimension is from the center of the inlet and outlet to the top of the interceptor One would specify a H dimension to meet the job requirements and the interceptor will be manufactured to that specification The extension is incorporated into the production of the interceptor to produce a seamless integral interceptor A sec...

Page 10: ...uations occur The extension is adjustable and is secured to the interceptor similar to a fixed extension After bolting the extension to the interceptor the top is adjustable to grade Installation Note If adjustable extension is install in areas other than on grade where fumes may seep from the adjustable extension connections an optional rope seal is recommended The 1 2 diameter neoprene sponge ga...

Reviews: