EN
Service tasks
AirConServiceCenter
102
9
Service tasks
9.1
Calibrating the oil scales
(for ASC2000G/ASC3000G only)
I
1. In the basic menu, use the cursor keys
or
to select
“Other
selections”
:
2. Press
ENTER
to confirm.
3. Use the cursor keys
or
to select
“Reset scales”
:
✓
You are then prompted to remove the containers from the scale:
NOTE
In order for the oil quantities and the UV additive to be measured
correctly, the zero point of the scales must be checked regularly and
reset if necessary.
Resetting is necessary:
If the quantity in a container deviates by more than 10 ml from the
target value
If the AirConServiceCenter has been shaken, for example during
transport on bumpy roads
Every four to six weeks
Short selection
Free selection
Other selections
ENTER-OK
Int. vessel filling
Flushing
Reset scales.
Service.
Remove the 3 Oil/UV
glasses from scales.
ENTER-OK STOP-EXIT
Summary of Contents for AirConServiceCenter ASC1000G
Page 2: ......