Initial start-up
7.6
Editing default values
The AirConServiceCenter has preset values for the most important
service tasks. The default values appear automatically when you select
the respective menu.
You can alter the following default values if necessary:
1. In the basic menu, use the cursor keys
or
to select
“Other
selections”
:
2. Press
ENTER
to confirm.
3. Use the cursor key
to select
“Service”
.
4. Press
ENTER
to confirm.
5. Enter the password
“7388”
.
6. Use the keypad and the cursor keys to enter the information.
7. Press
ENTER
to confirm.
8. Press
STOP
to access the standby menu.
Parameter
Default value
Pressure increase test time min.
5
Vacuum time min.
20
Leak test min.
4
PAG oil ml. (additional quantity)
5
UV tracer ml.
7
Filling Qt. g.
500
Print recovery value?
Yes
Short selection
Free selection
Other selections
ENTER-OK