Troubleshooting
Compressor does not run
(See table on page 25)
Fault
Possible cause
Remedy
U
T
= 0 V
The connection between the battery
and the electronics is interrupted
Establish a connection
Main switch defective (if installed)
Replace the main switch
Additional supply line fuse has blown
(if installed)
Replace the fuse
U
T
≤
U
ON
Battery voltage is too low
Charge the battery
Start attempt with
U
T
≤
U
OFF
Loose cables
Poor contact (corrosion)
Establish a connection
Battery capacity too low
Replace the battery
Cable cross section too low
Replace the cable
(
4
, page 4)
Start attempt with
U
T
≥
U
ON
Ambient temperature too high
–
Insufficient ventilation
Move the refrigerator
Condensor is dirty
Clean the condensor
Fan defective (if installed)
Replace the fan
Electric circuit between
the pins in the
compressor interrupted
Defective compressor
Replace the compressor
U
T
Voltage between the positive and negative electronic terminals
U
ON
Switch-on voltage of the electronics
U
OFF
Switch-off voltage of the electronics