EN
Troubleshooting
VAS 6380B / VAS 6381B
128
The display shows
“WARNING !
Not enough UV.
Add.
”
This message appears dur-
ing the filling process if there
is not enough UV additive in
the container to finish the
process.
Fill the UV additive container.
The display shows
“WARNING !
Not enough oil.
Add.
”
Message that appears during
the filling process if there is
not enough fresh oil in the
container to finish the pro-
cess.
Top up the fresh oil container
with a suitable oil type.
The display shows
“External tank empty
or closed valve !
Check!
”
Message that appears at the
start or during the filling of
the internal refrigerant con-
tainer if the set refrigerant
quantity cannot be attained.
Check if the external refriger-
ant container still contains
enough refrigerant or if the
valves of the external refrig-
erant container are open.
The display shows
“Change the equipment
drier filter.
Go on ?
”
This message appears when
you switch on the
AirConServiceCenter.
Change the internal filter as
soon as possible (chapter
“Changing the dryer filter” on
page 113). To skip this, press
ENTER
for 3 seconds.
The display shows
“Change the vacuum
pump oil.
Go on ?”
This message appears when
you switch on the
AirConServiceCenter.
Change the vacuum pump oil
as soon as possible (chapter
“Changing the vacuum pump
oil” on page 117). To skip
this, press
ENTER
for
3 seconds.
The display shows
“Printer not in line.
Carry on?”
Message indicates a printer
fault.
Check if there is paper in the
printer.
Check if the printer is
switched on (yellow LED
must light up constantly).
Check that the cover is
closed properly.
The display shows
“Error 01”
It was not possible to reduce
the pressure sufficiently
before the pressure increase
test.
Check air conditioner and
connections for leaks, con-
strictions and ice build-up.
Check pressure transducer
calibration.
The display shows
“Error 02”
Pressure increased again
with pressure increase test. It
is not possible to reduce
pressure sufficiently.
Check air conditioner and
connections for leaks, con-
strictions and ice build-up.
Check pressure transducer
calibration.
The display shows
“Error 03”
No data is coming from the
refrigerant scale.
Check the scale.
Problem
Cause
Remedy
WaecoVAS6380B-6381B_OPM_4445101232_EMEA(de-en-es-fr-ru)_202x-xx-xx.book Seite 128 Montag, 2. November 2020 1:46 13