EN
Initial start-up
VAS 6380B / VAS 6381B
90
7.9
Filling up the internal refrigerant container
When the AirConServiceCenter is started for the first time, the internal
refrigerant container must be filled from an external refrigerant tank with
at least 5000 g of refrigerant.
I
The current supply quantities are displayed in the standby menu.
There are three different types of refrigerant vessel available:
Refrigerant bottles without rising pipe:
These refrigerant bottles have
one
connection.
When filling the AirConServiceCenter, the connection must be on the
bottom (turn the bottle upside down).
Refrigerant bottles with rising pipe:
These refrigerant bottles have
one
connection.
When filling the AirConServiceCenter, the connection must be at the
top (place the bottle upright).
Refrigerant bottles with rising pipe:
These refrigerant bottles have
two
connections. To top up the
AirConServiceCenter, use the connection marked with
L
(= liquid).
When filling the AirConServiceCenter, the connection must be at the
top (place the bottle upright).
1. In the basic menu, use the cursor keys
or
to select
“Other selections”
:
2. Press
ENTER
to confirm.
3. Use the cursor keys
or
to select
“Int.vessel filling”
:
4. Press
ENTER
to confirm.
NOTE
Note the instructions on the refrigerant vessels.
S h o r t s e l e c t i o n
□
F r e e s e l e c t i o n
□
O t h e r s e l e c t i o n s
■
E N T E R - O K S T O P - E X I T
⬍
I n t . v e s s e l f i l l i n g
■
F l u s h i n g
□
R e s e t S c a l e s .
□
S e r v i c e .
□
WaecoVAS6380B-6381B_OPM_4445101232_EMEA(de-en-es-fr-ru)_202x-xx-xx.book Seite 90 Montag, 2. November 2020 1:46 13