EN-RATIOfresh-250-400_TI-MA-0809-11214900
21
After a Power Outage
The current time and all other settings are saved even dur-
ing a power outage. However, you should check all settings
and the time after power is restored to ensure the disinfec-
tion cycle is not started accidentally.
Frost Protection
Make sure the heating system remains in operation in case
of frost and that all rooms are sufficiently heated to prevent
frost.
Table 14 PRIMARY TEMPERATURE AND PUMP LEVEL SETTINGS
1
Tapping volume
flow (= HW) in l/
min
2
Pressure loss in
secondary circuit
(=HW side)
in mbar
3
Required
temperature in
primary flow,
in °C
4
Required
primary volume
flow,
in l/min
5
Return
temperature in
primary circuit
6
Pressure loss in
primary circuit
7
Output level of
the primary
circuit pump.
For RATIOfresh 250 at nominal hot water temperature of 45 °C
10
65
50
13.0
23
98
min
60
8.1
16
65
min
15
140
50
21.9
26
241
med
60
12.8
18
96
min
25
370
60
23.4
22
199
med
70
17.3
18
157
min
For RATIOfresh 250 at nominal hot water temperature of 60 °C
10
65
65
14.5
30
117
min
75
9.4
21
27
min
15
140
65
24.9
34
305
max
75
15.1
24
125
min
25
370
75
28.2
29
386
max
80
24
26
285
med
For RATIOfresh 400 at nominal hot water temperature of 45 °C
15
82
50
19.1
22
115
min
60
12.1
16
58
min
25
204
55
26.2
21
203
max
65
18.4
17
109
min
40
490
65
31.5
20
287
max
75
24.7
17
181
med
For RATIOfresh 400 at nominal hot water temperature of 60 °C
15
82
65
21.2
29
138
med
75
14
20
71
min
25
204
65
30.4
28
269
max
75
25.2
24
189
med
40
490
85
33.7
24
328
max
90
30.4
22
269
max