background image

6

EN-RATIOfresh-250-400_TI-MA-0809-11214900

2. Safety Information

The following safety information is intended to protect you
from hazards and dangers that may suddenly occur when
the device is handled incorrectly, either deliberately or un-
knowingly. We differentiate between general safety infor-
mation, explained on this page, and special safety informa-
tion, which is listed throughout the text of this manual. The
following symbols are important!

DANGER – possibility of personal injury
The following may occur during assembly or installation:
hazardous electrical shock, scalding, bruising/contusions,
and other adverse health effects. Please comply with the in-
structions marked with this symbol in the documentation.

CAUTION – possibility of property damage
This symbol indicates hazards that may result in damage to
components or a significant reduction of the functionality
of the system. Please follow the described assembly steps
and comply with the sequence of these steps.

NOTE – additional information
This symbol indicates useful notes, tips to make work
easier, and other information that may help you with the in-
stallation or operation.

2.1 Operator Qualifications

All tasks and activities involving the transport, installation,
as well as operation and servicing must be performed by
qualified technical personnel. We do not assume responsi-
bility or liability for damages resulting from noncompliance
with these instructions.

2.2 Intended Use

Function

Heated water from a storage tank is used with a plate heat
exchanger to prepare hot water with a constant tempera-
ture. The cooled down return water is layered into the lower
section of the storage tank.
This is controlled demand-dependent. Only when potable
water is withdrawn and detected by the single-jet meter,
the circulation pump feeds the exchanger with a variable
hot water volume stream from the storage tank so that a de-
fined tapping temperature is maintained.
The return temperature is the result of the storage tank tem-
perature, the pump speed, and the plate heat exchanger
design. The heat exchanger of the RATIOfresh freshwater

station is designed in such a way that the lowest possible re-
turn temperatures are reached, which exhibit only a minor
difference to the cold water temperature.

Thermal Disinfection

The Legionella Pneumophila Bacteria protection function
can be used to disinfect the entire hot water and circulation
piping network thermally and during freely selectable
times (day or week program). You choose between once
per week (Mon-Sun) or daily. This function serves to pre-
vent the formation of bacteria and viruses in the potable
water network.
The station uses an external relay output to activate the
buffer storage auxiliary or backup heating if the required
primary temperature (= disinfection temp. + hysteresis
dT

NH

) is not detected by the sensor T

buffer

. The display de-

picts “DISINFECTION.” If the required temperature exists
within the primary circuit (data logging with the tempera-
ture sensor “T

buffer

”), the thermal disinfection program

starts. The freely selectable disinfection temperature (e.g.
65 °C) is maintained across a settable time duration (e.g. 20
min) and across all flooded hot water and circulation pipes.
Unexpected malfunctions during the disinfection phase
are indicated to the user in plain text and additionally with a
visual signal (LED light,

fig. 10, no. 4

).

Potable water hygienists recommend a material tempera-
ture of 70 °C or higher for a duration of at least 3 minutes to
disinfect the piping network. The disinfection temperature,
however, should be a few degrees higher or the disinfec-
tion time somewhat longer to ensure proper disinfection
occurs. Do not forget to raise the branch lines to the hot wa-
ter tapping points to the required temperatures by with-
drawing water several times for several minutes.
Before activating the disinfection function, check whether
the hot water or circulation network can sustain such high
temperature stress (e.g. damaging galvanized steel pipes)
and whether the carbon hardness of the potable water is
within an acceptable range.
The hot water users are at risk of scalding injuries while the
disinfection program is running. The disinfection should
therefore be carried out at night.

Circulation

The temperature difference is calculated from the circula-
tion flow and return temperature and compared with the
preset nominal difference. If the temperature difference is
too small, the control detects an oversupply of the circula-
tion and reduces the output of the circulation pump based
on the deviation. If the temperature difference is too great,
the control increases the output of the circulation pump
based on the deviation. The mass flow is then varied
through a pulsed modulation of the pump output. If an ad-
justable return temperature is exceeded, the controller
switches the pump off.

Summary of Contents for RATIOfresh 250

Page 1: ...ely asdelivered Numerous Application Options The freshwater station can be combined with almost any heat source Oil gas wood logs and pellet boilers are as suitable as a solar installation or local or district heating dis tribution systems All it takes is a buffer cylinder whose ther mal stratification is supported by minimal return tempera tures within the primary circuit Protection from Legionel...

Page 2: ... C 5 25 K Pressure loss Dp secondary 370 mbar with 25 l min Voltage supply 230 V 50 Hz Fuses Operating voltage 230 V control fuse 100 mAT 250 V power fuse 2 AT 250 V To replace internal fuses de energize the device remove the screws on the controller and lift off cover fig 8 9 10 Dimensions of housing H x W x D 940 x 350 x 181 mm Color powder coated Upper section RAL 7035 light gray Bottom section...

Page 3: ...ping capacity 10 C 45 C sec 10 C 60 C sec 40 l min 98 kW 139 kW Coefficient of performance NL 10 C 45 C sec 82 C prim acc to DIN 4708 T3 10 C 60 C sec 85 C prim 10 C 60 C sec 75 C prim NL 19 5 NL 17 NL 11 Nominal hot water temperature 25 70 C Circulation return 5 70 C 5 25 K Pressure loss Dp secondary 490 mbar with 40 l min Voltage supply 230 V 50 Hz Fuses Operating voltage 230 V control fuse 100 ...

Page 4: ...n 1 Controller 2 Heat ex changer 85 57 80 ø 55 ø 55 181 350 80 7 Hot water 6 Cold water 9 Single jet meter 3 Circulation pump 10 Housing 8 Circulation Frontal view Top bottom view Drill pattern 64 32 254 521 827 70 Figure 2 RATIOfresh freshwater station viewed sectionally with dimensions and drilling template ...

Page 5: ...f valve 5 Primary return connection T 1 OT flat sealing made from brass with pump shut off slider incl backflow preventer 6 Cold water supply connection T1 OT flat sealing made from brass 7 Hot water outlet connection T 1 OT flat sealing made from brass 8 Circulation return connection option T IT closed with plug 9 Single jet meter brass chrome plated connections OT flat sealing QN 2 5 m h 10 Bott...

Page 6: ... protection function can be used to disinfect the entire hot water and circulation piping network thermally and during freely selectable times day or week program You choose between once per week Mon Sun or daily This function serves to pre vent the formation of bacteria and viruses in the potable water network The station uses an external relay output to activate the buffer storage auxiliary or b...

Page 7: ...t be checked regularly in accordance with DIN 4753 Theexhaust vent maynever be closed or restricted A corresponding water filter meeting current technology standards isto be installed intothecold water supplyline Connecting the Circulation The freshwater station RATIOfresh is designed to be con nected to a circulation line The circulation pump must be a commercially available stepped wet pump E pu...

Page 8: ...nsert in cluded plugs 2 Insert screws 3 to a distance of 1 cm and insert housing 4 into keyholes 5 and attach screws Tighten screws 3 firmly 3 3 Storage Tank Mounting fig 5 The RATIOfresh freshwater station is suitable for mounting directly on all buffer cylinders RATIO H series using the additionally available tank expansion kit cf accessories table 4 Remove the insulation of the RATIO H 1 cylind...

Page 9: ... 10 into the cold and hot water lines in close proximity to the station After irrigation cock 10 in the hot water line an addi tionalshut off cock 11 isneeded forflushingthepipes 3 5 Connecting Circulation Optional fig 6 DVGW 551 specifies a circulation element or system in larger hot water networks The circulation return 21 must be installed directly before tapping point 22 The circula tion pump ...

Page 10: ...maryflow are installed in an upward direction Connect the primary return line 8 and route to the cor responding storage tank connection that matches the temperature level Table 14 lists the return temperatures of the station in dependency of the operating condi tions Route cable of the temperature sensor 9 marked Tprim from the freshwater station along the primaryflow and attach sensor in the aux ...

Page 11: ...same way and plug into socket 7 required cable cross section 3 x 0 75 to 1 5 A fourth temperature sensor type KTY cf accessories can be connected via plug 8 and socket 9 A RS 232 interface cable available as an accessory can be connected to plug 12 socket 13 It is also possi ble to log all measured values the current controller sta tus and the current pump output This requires connect ing the 9 pi...

Page 12: ... P1 PE L N P2 PE L N Low voltage area 230 V 5V 15V R T 10 9 11 3 13 9 19 15 5 21 7 16 17 14 18 8 10 12 6 20 4 at rest 11 12 13 activated 11 12 13 Hot cold water sensors Hot water sensor blue Mass brown Circulation cold water sensor blue Primary circuit sensors Buffer cyl sensor blue Mass brown Primary flow sensor blue Optional data cable Plus 5V yellow TxData white RxData green Mass brown Optional...

Page 13: ... temperature level Use keys 6 and 8 to browse within the info level anddepict allcurrent temperatures andpumpoutputs 4 2 Controller Settings fig 10 Use key 7 to switch from the info level to the menu level Use keys and to select the desired setting menu Press key to switch to the value level where the set nominal values are listed in square brackets Select the desired menu item with the and keys a...

Page 14: ...nday Sunday 00 00 to 24 00 Table 6 Menu Level use the and keys to select the desired menu and confirm with the key Menu Description SETTINGS HOT WATER Settings for the primary circuit pump nominal hot water temperature and standby temperature details in Table 7 SETTINGS CIRCULATION Settings for the circuit pump operating mode determining the time frame for the circulation operating circulation ret...

Page 15: ...ange here 0 l min to 20 l min is divided by the control into 10 time slots and an internal control value is adjusted for each time window during the adaptation process Selecting an unfavorable max tap volume value can thus adversely affect the control performance The actual max output of the station is not reduced by this setting 20 to 80 l min 20 l min END Use the and keys to select and then conf...

Page 16: ...sk of scalding during the disinfection cycle MODE Nominal OFF Select operating mode for the disinfection of the hot water system When in automatic mode AUTO the hot water and circulation network are thermally disinfected at the selected time Select a time outside of the typical tapping times to reduce the risk of scalding With the operating mode ON the disinfection is activated continuously e g fo...

Page 17: ... of pump in relation to drawn water volume 1 50 K 5 K RATIOfresh type 250 400 Controlling variation this selection resets all values to factory setting 250 400 800 250 400 ADAPTATION VALUES Start values for calculation of pump power For all 10 tapping slots start values are set They are the base of calculating the required pump force The actual temperatures and tapping volumes are incorporated in ...

Page 18: ...used for the manual operation of the pump OFF ON AUTO AUTO BOILER REQUEST AUTO Software can be used to set the operating mode of the potential free relay and is used for manual operation OFF ON AUTO AUTO END Select this menu item with the and keys and press the key to return to the menu level Table 13 Value Level SETTINGS LANGUAGE Designation Description Range Base value Your value LANGUAGE Englis...

Page 19: ...for the specific on site condi tions fig 10 provides an overview over the menu structure and explains the use of the control keys Enter the corre sponding values into the setting menus in the following order HOT WATER CIRCULATION DISINFECTION SERVICE LANGUAGE and TIME Tables 7 to 13 pro vide assistance with selecting the respective values To finish enter the individual configuration into the Your ...

Page 20: ...t tapping volumes a controlled tapping should be per formed when initially starting up the system Please follow these steps and adhere to the described sequence of these steps 1 First select the menu item Tapping Area in the info level of the controller 2 Open a hot water tap until the display depicts 02 3 After approx 30 seconds the controller starts to adjust the hot water temperature to the des...

Page 21: ...ature in primary circuit 6 Pressure loss in primary circuit 7 Output level of the primary circuit pump For RATIOfresh 250 at nominal hot water temperature of 45 C 10 65 50 13 0 23 98 min 60 8 1 16 65 min 15 140 50 21 9 26 241 med 60 12 8 18 96 min 25 370 60 23 4 22 199 med 70 17 3 18 157 min For RATIOfresh 250 at nominal hot water temperature of 60 C 10 65 65 14 5 30 117 min 75 9 4 21 27 min 15 14...

Page 22: ...o 5 in the primary circuit flow and pump slider fig 11 no 7 to block primary cir cuit fig 11 no 2 9 Empty heat exchanger fig 11 no 3 on the primaryside by loosening the 1 bolt fig 11 no 6 at the primary flow connection and fig 11 no 10 at the primary re turn To remove the heat exchanger remove all four 1 swivel nuts fig 11 no 4 6 10 11 using a size 36 wrench Place heat exchanger over night into a ...

Page 23: ...ue with the recommendations in table 14 and correct as needed Incorrectly set power output level of the primary circuit pump Compare the set value with the recommendations in table 14 and correct as needed Controller not yet adapted Carry out a controlled tapping see chapter 5 6 Air within the primary circuit prevents sufficient flow through the heat exchanger Bleed the primary circuit see chapter...

Page 24: ... circulation system Only without circulation system Very low tapping volume with very high primary circuit temperature falls below the controller limit range Reduce the primary circuit temperature It takes a long time until hot water emerges from the tapping point Incorrectly set circulation Check the circulation settings Circulation and standby function deactivated due to a primary circuit temper...

Page 25: ...EN RATIOfresh 250 400_TI MA 0809 11214900 25 ...

Page 26: ...26 EN RATIOfresh 250 400_TI MA 0809 11214900 ...

Page 27: ...runs the speed controlled hot water circulation pump If temperatures in the primary buffer cylinder are sufficient solar heat is used for heating by raising the heat ing return temperature 9 System Solutions Example RATIO H PG RATIOfresh T P2 T T Vm T T SUNGO P4 P5 HKM P1 P1 CIRCO P3 Solar controller T storage Heating circuit Collector field P1 Solar circuit pump P2 Cylinder charge pump P3 Heating...

Page 28: ...ge is utilized for space heating The solar controller additionally controls loading of the buffer via the fireplace inset Tvl SUNGO Vu Ta Ttw P1 P1 CIRCO P4 P3 Vr B A AB P2 P5 RATIOfresh RATIO H PG Heating circuit Solar controller T storage Collector field Oil or gas heating boiler Cold water Hot water P1 Solar circulation pump P2 Buffer discharge pump to heat potable water P3 Cylinder charge pump...

Reviews: