4

  

EN-XXX_ECOplus-Solar-Storage_MA-201026-1WA10603

Figure 4  Drinking water connections (example): 

Air vent; 

10

 Magnesium protection anode with cable; 

11

 Cold water; 

12

 Hot water; 

13 

Safety 

unit; 

14

 Circulation pump; 

15 

Thermostatic mixer; 

16

 Check valve; 

17

 Filling and emptying tap

3.3  Connecting the Domestic Water 

Circuit

 

(Fig  4) Connect a safety unit (13) to the cold water sup-
ply and ideally position above the storage  This allows 
for easy maintenance of the safety group without having 
to 

empty 

the 

tank  

     

 

The storage tank might be damaged without safety 
group or when the safety group is closed off!  

 

The water expands when heated and thus high over-
pressure can build up in the system  Ensure that there 
is no shut-off valve between cylinder and safety valve  

 

Installation of a filling and emptying tap at the lowest 
storage connection (17) 

 

Fit a thermostatic mixer (15)  This assures that even 
when the storage tank is heated to its maximum tem-
perature the DHW temperature set at the thermostatic 
mixing valve will not be exceeded  If no thermostatic 
mixer is fitted, maximum vessel temperature must 
be limited to 65 °C at the solar controller  

 

 

Serious danger of scalding! 

 

  

The solar installation may heat the storage water to tem-
peratures of up to 95 °C.  

 

 

 

.  

The installation of a thermostatic mixing valve limits the 
tap temperatures to a safe temperature level 

 

Installation of a circulation pump if required (14)  The 
return should be taken from close to the tapping point  
The circulation pump should govern circulation ac-
cording to water temperature (temperature sensor) 
and with a timer 

 

The circulation control should be implemented in the 
most energy saving fashion according to the state of 
the art  

 

Installation of an air vent (9)  Part of the ECOplus con-
nection kit, part no  139 002 07 

13

15

14

17

11

12

16

9

10

8 Cold water connection

3 Circulation connection

CONVECTROL  

part of the ECOplus 

connection kit,  

part no  139 002 07

1 Hot water connection

16

9

10

8 Cold water connection

3 Circulation connection

1 Hot water connection

11

Summary of Contents for ECOplus

Page 1: ...ration 2 3 2 Setting up the Storage 2 3 3 Connecting the Domestic Water Circuit 4 3 4 ConnectingtheSolar andAuxiliary Heating Circuit 5 3 5 Connecting Backup Heater 5 3 6 Installing Temperature Sensors 5 3 7 Install a Impressed Current Anode 6 4 Startup of the System 6 4 1 Acceptance Protocol 6 4 2 System Check 6 4 3 Flushing the Installation 6 4 4 Settings at Boiler and Solar Controllers 6 4 5 Fi...

Page 2: ...the filled tank Wagner Solar cannot be held liable for damages resulting from improper use 2 Scope of supply The ECOplus solar cylinder is supplied standing upright and screwed onto a pallet The serial no is located on the type label Table 1 Scope of supply fig 2 1 Storage 2 Jacket insulation with hook ratchet closure may be several parts depending on storage type 3 Insulation plug with cap for ac...

Page 3: ...EN XXX_ECOplus Solar Storage_MA 201026 1WA10603 3 Figure 2 Scope of supply Figure 3 Tilt the storage to insert the inner floor insulation 2 4 8 7 1 6 5 2 3 ...

Page 4: ...s heated to its maximum tem perature the DHW temperature set at the thermostatic mixing valve will not be exceeded If no thermostatic mixer is fitted maximum vessel temperature must be limited to 65 C at the solar controller Serious danger of scalding Thesolarinstallationmayheatthestoragewatertotem peratures of up to 95 C The installation of a thermostatic mixing valve limits the tap temperatures ...

Page 5: ...available that can be installed in the 1 socket on the side fig 6 Please observe instructions supplied with the respec tive heating device Laying the mains cable of the electrical heater a heat resistant cable min up to 95 C must be used when laying the cable under the insulation jacket The immersion heater must only be connected to mains after the storage tank is filled If no immersion heater is ...

Page 6: ...allation Malfunction or damage when storage tank is not ade quately purged In spite of careful production methods some residues of the processes including metal slack may remain inside the pipes the vessel and the heat exchangers These can cause problems during operation of the system and may lead to damage Therefore the system must be flushed before permanent operation starts Also filtering retai...

Page 7: ...ar cylinder 1 Now set the insulation jacket to the connection side around the connection openings and if in place the immersion heater 2 First lock the ratchet closure into the loosest position and then tighten from the top alternating if the jacket has more than one closure until the jacket tightly fits the storage tank 3 If no immersion heater is fitted insert insulation plug with cap 4 Insert i...

Page 8: ... in uninsulated sacrificial magne sium anode examine remaining magnesium mass and if necessary install new anode Forsacrificialanodeswithinsulatedinstallation MGan odes test the protective current between storage and anode fig 13 When the value is below 0 3 mA remove and examine the anode and replace if required If an impressed current anode is installed observe the related product documentation A...

Reviews: