63
GA 5000EAC
OPERATING MANUAL
VERSION 09/2016
ORDER NUMBER DOC2360922
Incorrect maintenance/repair!
Danger to life and equipment damage.
Repair or replacement of devices or parts of devices are only
allowed to be performed outside the hazard area by qualifi ed
personnel.
DANGER
8.2
MAINTENANCE
Maintenance work should be undertaken regularly and carefully by qualifi ed and trained
staff . They should be informed of specifi c hazards during their training.
The following hazards may arise during maintenance work:
- Health hazard from inhaling solvent vapors
- Use of unsuitable tools and aids
An authorized person must ensure that the device is checked for being in a reliable state
after maintenance work is completed.
8.2.1
MAINTENANCE STAFF
8.2.2
SAFETY INSTRUCTIONS
Observe the safety instructions in Chapter 4 and Chapter 8.1.2.
Prior to maintenance
- Flush and clean the system Chapter 8.1.3.
After maintenance
- Carry out a safety checks in accordance with Chapter 8.2.3.
- Put the system into operation (Chapter 6.6) and check for leaks.
- Carry out a function test, if required, in accordance with Chapter 11.
In accordance with the guideline for liquid ejection devices (DGUV regulation 100-500):
- The liquid ejection devices should be checked by an expert (e.g., WAGNER service
technician) for their safe working conditions as required and at least every 12 months.
- For shut down devices, the examination can be suspended until the next start-up.