TITANUS
SUPER·SENS
®
Installation
TSS_05_B-en-e Data:
02/09
5
– 9
5.5
Mounting
Location
5.5.1 Fixing of the air sampling system TITANUS
®
pipe adapter
type RA-AD2
arcs/elbows 90°
air sampling pipe
Fig. 5.5: Protection against impurities and dripping water during the installation of
TITANUS
®
Mount the air sampling system so that the displays are clearly visible. If
necessary install a remote display unit. The air sampling smoke detection
system is either directly mounted on a wall with its bottom casing or by
means of a special support (refer to chapter 2.2.5 "Device Supports").
The air outlet of the air sampling smoke detection system is not allowed
to be blocked. The distance between the air outlet of TITANUS
®
and e.g.
a wall is to be at least 10 cm.
The air sampling system TITANUS
®
can be mounted with the air sam-
pling pipe connectors pointing upwards or downwards. If necessary turn
the lid by 180°.
Aspiration Downwards
If
TITANUS
®
is mounted with the air sampling pipe connectors pointing
downwards it is to be guaranteed that no impurities or dripping water en-
ter the air outlet which then points upwards. If necessary use the pipe
adapter with a short pipe curving downwards (refer to
0H
Fig. 5.5).
Mounting Material
TITANUS
®
cylinder or flat head screws
– diameter of thread: max. 6 mm
– diameter of head: 10 up to 12 mm
Support
(type H-AD2)
cylinder or flat head screws
– diameter of thread: max. 4 mm
– diameter of head: 5 up to 7 mm