Installation
TITANUS
SUPER·SENS
®
5
– 12
Data: 02/09
TSS_05_B-en-e
5.6 Electrical
Connection
In order to prepare the electrical connections follow the steps below:
1. Break through the cable entries e.g. by means of a screw driver.
2. Attach the plastic connection pieces PG16 or PG11.
3. Pass the cable through the corresponding PG-entries and a ferrite
ring each.
4. Pass the metallic grounding cable through the insulating hose.
Insulate the metallic grounding cable by the included hose so that a con-
tact with the metallic detector head is avoided.
The electrical connection is effected via terminal block X1 and X2 on the
base board of TITANUS
®
. Pay attention to the allowed cable cross sec-
tions of the corresponding screw joint and the allowed wire cross sec-
tions of the terminals (refer to chapter 3 "Technical Data").
The relay contacts on the base board can be used e.g. for the connection
to a central fire panel or the triggering of signal devices, guiding systems
etc.
If the "alt Sense"-output has a permanent voltage of +24V the sensitivity
is automatically switched to the next less sensitive level.
If the voltage at the reset-input is perma24V all signals (action
and fire alarm included) are automatically reset if the cause of the fault
has been eliminated (action and fire alarm are non-latched).
Connection works are only allowed if the device is current less.
INSTRUCTION
TIP
ATTENTION