TITANUS
SUPER·SENS
®
Installation
TSS_05_B-en-e Data:
02/09
5
– 17
5.7 Application of TITANUS
®
and fire detc-
tion system AlgoRex
®
In general, there are different possibilities to connect the potential-free
alarm and fault contacts of the air sampling smoke detection system
TITANUS
®
to the smoke detection system
AlgoRex
®
.
•
the collective connection
•
the use of line modules of the AnalogPLUS
®
-technology
•
the connection by means of interactive line modules
5.7.1 Collective connection
TITANUS
®
can be connected to a collective line board (belongs to the
central unit) of the smoke detection system
AlgoRex
®
. For each used
alarm contact a collective detection line is required. It is possible to con-
nect the fault contact either separately to the collective line board or to in-
tegrate it into the alert alarm-detection line.
2H
Fig. 5.13
illustrates the cor-
rect connection at TITANUS
®
.
Pay attention to the correct polarity when using the 5.6V-Z-diodes.
INSTRUCTION