Installation
TITANUS
SUPER·SENS
®
5
– 24
Data: 02/09
TSS_05_B-en-e
5.8.1 Mounting of the contact coupler SPF 5300
for the extension
Fig. 5.18: Mounting of the contact coupler SPF 5300
Mounting in TITANUS
®
In order to install the contact coupler SPF 5300 into the air sampling
smoke detection system TITANUS
®
follow the steps below:
Open the device according to chapter 5.2.
Screw the top hat rail (A) onto the support angle (B). Use 2 flat
head screws (C) M3x6, 2 tooth lock washers (D) and 2 hexagon
nuts (E) M3.
Screw the support angle and the top hat rail (F) into the air sam-
pling system. Use the 2 self-cutting screws (G).
Lock the SigmaSys-contact coupler SPF 5300 (H) edgewise on
the top hat rail.
Connect the contact coupler (H) to TITANUS
®
according to the
connection plan (refer to chapter 5.8.2).