Installation
TITANUS
SUPER·SENS
®
5
– 32
Data: 02/09
TSS_05_B-en-e
5.11 Data Log
The device can be tested by means of a diagnostic device. Besides the
current air flow sensor data different status values can be read out, which
helps to register modified operating conditions during service. In addition,
air flow values can be directly read out by means of a laptop. A third pos-
sibility is to receive this data through a pre-fabricated cable (diagnostic in-
terface) via a PC. The two wires (wh, br) of the pre-fabricated cable are
connected to the terminals X2.16 and X2.17 of TITANUS
®
or to the ter-
minals X1.7 and X1.8 ("+ Data" und "- Data") of the remote display unit
(refer to
6H
Fig. 5.27). The Sub-D-plug with 9 poles is linked to the COM-
Port (COM1 or COM2) of the PC and the diagnostic software is started.
Fig. 5.27: PC-connection via the diagnostic interface