TITANUS
SUPER·SENS
®
Installation Pipe System
TSS_06_A-en-e
Data: 02/09
6
– 11
6.5
Filter
6.5.1 Installation of air filter, type LF-AD-x
11
0
90
Fig.
6. 7: Spacing for bore holes on base of air filter housing
Air Filter LF-AD-x
1
.
To fit the filter into the pipe system, use the two PG29 filter screw-
joints.
2. Fix these screw-joints in the same way as the pipe adapter.
3. When installing the filter, ensure that the direction of air flow is shown
at the side of the housing’s bottom part.
4. Screw the bottom part of the housing directly to the wall.
Installation Material
Air Filter
cylinder or flat-head screws
– thread diameter: max. 4 mm
– head diameter: 5 to 7 mm