Commissioning
TITANUS
SUPER·SENS
®
7
– 2
Data: 02/09
TSS_07_A-en-e
7.1 Adjustment air flow sensor
In order to adjust TITANUS
®
correctly to the pipe system, the device
must be in operation for at least 30 minutes.
Adjustment Types
z
The air flow sensor adjustment depends on the current air pressure
(refer to chapter 7.1.1 "Adjustment Dependent on the Air Pressure").
Refer to the air pressure adjustment charts in the appendix.
z
The adjustment can be independent of the current air pressure (refer
to chapter 7.1.2 "Adjustment Independent of the Air Pressure").
In any case the adjustment type is to be written down in the commission-
ing protocol in order to judge the air flow sensor value correctly when the
system is maintained.
7.1.1 Adjustment dependent on the air pressure
Fig. 7.2: Adjustment dependent on the air pressure of the air flow sensor of
TITANUS
®
INSTRUCTION