Commissioning
TSS_07_A-en-e Data:
02/09
7
– 5
7.2 Detector head and alarm transmission
Trigger the alarm of the smoke detector and check the transmission to
the central fire panel as follows:
1. Spray test aerosol either into the first air sampling point or into the
test adapter of TITANUS
®
.
2. Follow the steps in the table.
Check to see if...
If this is not the case...
the air sampling smoke detection
system displays an alarm.
1. verify that the display board is connected.
2. the air sampling system is damaged.
3. exchange the detector head.
the alarm signal is transmitted to
the central fire panel and on the
corresponding line.
1. check the transmission cables.
Record all tested data in the inspection protocol.
7.3 Air Flow Monitoring
Pipe Fracture
Verify the detection of pipe fractures:
1. Loosen the connection between pipe and TITANUS
®
or open the test
adapter.
2. Verify if the fault display of the air sampling smoke detection lights.
3. Check optionally the data of the air flow sensor by means of the diag-
nostic device and a PC or laptop.
4. Register the result in the commissioning protocol.
Blockage
Verify the detection of blockages:
1. Close the necessary number of air sampling points by means of adhe-
sive tape according to the project planning of the air flow monitoring.
2. Verify if the fault display of the air sampling smoke detection system
lights.
3. Check optionally the data of the air flow sensor by means of the diag-
nostic device and a PC or laptop.
1. Register the result in the commissioning protocol.
INSTRUCTION