Commissioning
TITANUS
SUPER·SENS
®
7
– 6
Data: 02/09
TSS_07_A-en-e
Trouble Shooting
If faults in the air flow are not correctly detected by the device do the fol-
lowing:
Check to see if...
1. all air sampling points are free.
2. the pipe system has fractures or cracks.
3. all pipe connections are tight.
4. the ventilator is unblocked.
5. the correct aspiration-reducing film sheets have been used.
If no faults are detected the functionality of TITANUS
®
or the air flow sen-
sor is checked by means of the testing pipe or through the diagnostic
evaluation (refer to chapter 7.5 "Operational Check of TITANUS
®
")
.
7.4 Fault signal transmission
The following steps can only be effected 5 minutes after having triggered
the air flow adjustment according to chapter 7.1 "Adjustment of the Air
Flow Sensor".
1. Check the fault signal transmission.
Check the air flow monitoring (according to the following section) to see if
the fault is still indicated at TITANUS
®
and, if necessary, at the central fire
panel.
INSTRUCTION