8
Maintenance
8.1
Visual
Check
Check to see if
z
the pipe system is mounted tightly, undamaged and easily accessible.
z
the air sampling points of the pipe system are unblocked.
z
the air sampling pipe and the connection cable are connected tightly.
z
the device support is fastened properly – if installed.
z
the air sampling smoke detection system is damaged-
8.2 Smoke Detector and Alarm Transmis-
sion
Proceed according to chapter 7.2 "Detector Head and Alarm Transmis-
sion". In addition, check the detector head through visual check for exter-
nal dirt and, if necessary, exchange it. Pay attention to the drift display at
the diagnostic device.
8.3
Pipe
System
In areas where dust particles or icings may occur check the pipe system
and the air sampling points for blockage. If necessary, blow-out the pipe
system and the air sampling points by means of compressed air. Use
prophylactic ally a transportable compressed air bottle (blowing-out sys-
tem) or the installed manual blowing-out system.
Before the pipe system is blown-out disconnect TITANUS
®
from the pipe
system in order to avoid damaging the air flow sensor.
In order to adjust TITANUS
®
correctly to the pipe system, the device
must be in operation for at least 30 minutes.
ATTENTION
INSTRUCTION