Technical Description
TITANUS
SUPER·SENS
®
2
– 18
Data: 02/09
TSS_02_B-en-e
2.3.2 Air sampling points for room monitoring
2.3.2.1
Aspiration-reducing film sheets
Fig. 2.12: Air sampling point with aspiration-reducing film sheet and marking tape
An air sampling point is a 10 mm-hole in the air sampling pipe. This hole
is sealed by means of a patented aspiration-reducing film sheet which
has an opening of the required diameter. The size of the opening de-
pends on the design of the pipe system (refer to chapter 4, "Project Plan-
ning").
In order to avoid the aspiration-reducing film sheet from loosening it is
fixed with a marking tape which is transparent with red edges and a
10 mm-hole. The marking tape is adhered onto the aspiration-reducing
film sheet in such a way that the air sampling point will not be covered
and remains visible even from far distances.