Technical Description
TITANUS
SUPER·SENS
®
2
– 22
Data: 02/09
TSS_02_B-en-e
2.3.5 Air return for pressurised and dusty areas
Fig. 2.16: Air return with
TITANUS
®
If the air sampling smoke detection system TITANUS
SUPER·SENS
®
and the pipe system are installed in two areas P1 and P2 with different
air pressures the air is to be returned to the pressure area of the pipe
system (refer to
0H
Fig. 2.16). The air return can be used for a pressure
compensation or in order to keep the air clean (e.g. from odours) in neigh
boring rooms.
TITANUS
®
pipe adapter
screw joint
PG29
air return
air sampling pipe
blind plug
Fig. 2.17:
TITANUS
®
with pipe adapter
The return air pipe system is connected to the pipe adapter type RA-AD2
which is mounted onto the air outlets of the TITANUS
®
(refer to
1H
Fig.
2.17). The remaining output of the pipe adapter is closed through a blind
plug.