Technical Description
TITANUS
SUPER·SENS
®
2
– 24
Data: 02/09
TSS_02_B-en-e
2.3.7 Steam trap for humid areas
Fig. 2.19: Steam trap to eliminate water vapour from the pipe system and to collect the con-
densate from the pipe system
If TITANUS
®
is used in environments with high humidity condensate can
occur in the air sampling system. In order to collect this condensate the
steam trap is installed at the deepest point of the pipe system before the
air filter and the air sampling smoke detection system. The 45°-elbows
permit an optimum distance to the wall (refer to
2H
Fig. 2.19).
The steam trap can be operated in a temperature range between 0°C
and +50°C. The sinter filter in the steam trap has a pore width of 50 µm
and absorbs coarse dirt particles.
The steam trap is used in the following areas:
Application
z
areas with high temperature variations
z
areas with fresh air supply