TITANUS
SUPER·SENS
®
Technical
Data
TSS_03_A-en-e
Data: 02/09
3
– 3
TITANUS
SUPER·SENS
®
Display Sensitivity
Level
Sensitivity
I
0.02% light obscuration/m
II
0.01% light obscuration /m
III
0.005% light obscuration /m
IV
0.0025% light obscuration /m
3.2 Accessories – TITANUS
®
Remote displays for
TITANUS SUPER·SENS
®
Remote Displays
voltage
15 to 30 V DC
current consumption (at 24 V)
quiescent
maximum
10 mA
65 mA
electrical connection lengths
1 remote display
2 remote displays
total length max. 1000 m
total length max. 500 m
protection class
IP 45
Displays
displays at the device
level display
alarm
fault
ON
diagnostics
smoke level 1 to 10
action, alert and fire alarm
collective fault
operation display
infrared-LED for device data
Connectors
terminal block
terminals for
wires of max. 2.5 mm²
cable entry
2 x PG9