Pipe Design
TITANUS
SUPER·SENS
®
4 –
10
Data: 02/09
TSS_04_A-en-e
4.1.5 Project planning limits
The following limit values must be complied with at all times with the
TITANUS
®
per pipe system connected
:
z
The minimum pipe length between 2 aspiration apertures is
4 m
.
z
The maximum pipe length between 2 aspiration apertures is
12 m
.
z
The maximum overall pipe length is 200 m.
z
The maximum monitoring area per sampling aperture corresponds to
the monitoring area of point-shaped detectors in accordance with the
applicable project planning guideline.
z
A maximum of
24
aspiration apertures are possible per detector
module.
The maximum overall monitoring area, the maximum overall pipe length
and the maximum number of aspiration apertures are independent of the
project planning selected, as are the restrictions from national regula-
tions.