Pipe Design
TITANUS
SUPER·SENS
®
4 –
16
Data: 02/09
TSS_04_A-en-e
Results:
The following modules may optionally be used with the corresponding
settings for class B or A:
z
setting the sensitivity on 0,025 % LT/m
z
setting the sensitivity on 0,05 % LT/m
z
setting the sensitivity on 0,1 % LT/m
z
setting the sensitivity on 0,2 % LT/m
Possible system parameters:
z
U- pipe system
-
12 V fan voltage, max. 90 m overall pipe length
-
15 V fan voltage, max. 130 m overall pipe length
z
M- pipe system,
-
12 V fan voltage, max. 120 m overall pipe length
-
15 V fan voltage, max. 170 m overall pipe length
z
Double U- pipe system,
-
12 V fan voltage, max. 140 m overall pipe length
-
15 V fan voltage, max. 200 m overall pipe length