TITANUS
SUPER·SENS
®
Pipe
Design
TSS_04_A-en-e
Data: 02/09
4 –
17
4.2.4
Aperture
diameter
The aperture diameters of the aspiration apertures can be found in the
corresponding table for the respective pipe configuration:
I-Pipe
A
B
C
D
E
L
TITANUS
d
Fig. 4.3: I –pipe system
Aspiration apertures
Number of
apertures
1 2 3 4 5 6 7 8 9
10
11
12
Sampling
aperture
∅
in mm
0F
1)
A
10.0 6.0 5.2 4.6 4.2 3.8 3.6 3.4 3.0 3.0 2.5 2.5
B
—
6.8 5.2 4.6 4.2 3.8 3.6 3.4 3.0 3.0 2.5 2.5
C
—
—
5.6 4.6 4.4 4.0 3.8 3.4 3.2 3.0 3.0 3.0
D
— — —
5.0 4.4 4.0 3.8 3.4 3.4 3.0 3.0 3.0
E
— — — —
4.4 4.2 3.8 3.6 3.6 3.4 3.0 3.0
F
— — — —
—
4.2 3.8 3.8 3.6 3.4 3.4 3.0
G
— — — —
—
—
4.0 3.8 3.6 3.6 3.4 3.2
H
— — — —
—
—
—
4.0 3.8 3.6 3.4 3.2
I
— — — —
—
—
—
—
3.8 3.6 3.6 3.2
J
— — — —
—
—
—
—
—
3.8 3.8 3.2
K
— — — —
—
—
—
—
—
—
3.8 3.8
L
— — — —
—
—
—
—
—
—
—
4.0
1
Press cut diameter in aspiration-reducing film sheet