Pipe Design
TITANUS
SUPER·SENS
®
4 –
20
Data: 02/09
TSS_04_A-en-e
4.3 Special project planning
4.3.1 Project planning for individual aperture monitoring
The following system parameters apply to the detection of an individual
or a particular number of blocked aspiration apertures, depending on
pipe configuration.
The specifications according to Chapter 4.2 apply to project planning.
The following limit values and aperture diameters should also be taken
into account. Additional accessories (air filters, condensation separators,
etc.) can influence the maximum pipe length.
4.3.1.1 I-Pipe
system
TITANUS
®
A
B
C
D
E
I
J
F
TITANUS
d
®
Fig. 4.7: I-Pipe system for area protection
Limit values
Min. distance from TITANUS
®
to 1
st
sampling aperture
4 m
Max. distance from TITANUS
®
to 1st sampling aperture
20 m
Max. Distance from 1
st
sampling aperture to last
50 m
Max. Overall pipe length per pipe system
70 m
Min. distance between 2 aspiration apertures (d)
4 m
Max. distance between 2 aspiration apertures (d)
12 m
Max. number of aspiration apertures (n) per pipe system
10 pcs.