Pipe Design
TITANUS
SUPER·SENS
®
4 –
22
Data: 02/09
TSS_04_A-en-e
4.3.1.2 U-Pipe
system
TITANUS
®
A
B
C
D
E
H
®
d
TITANUS
®
Fig. 4.8: U-Pipe system for area protection
Limit values
Min. distance from TITANUS
®
to T-piece
4 m
Max. distance from TITANUS
®
to T-piece
20 m
Max. Branch length
60 m
Max. Overall pipe length per pipe system
120 m
Min. Distance between 2 aspiration apertures (d)
4 m
Max. Distance between 2 aspiration apertures (d)
12 m
Max. number of aspiration apertures (n) per pipe system
16 pcs.
Aspiration apertures
Number of aper-
tures
per pipe system
2 4 6 8 10
12
14
16
Sampling aperture
∅
in mm
6F
7
)
A
B
C
D
E
F
G
H
7,0
—
—
—
—
—
—
—
5,0
5,2
—
—
—
—
—
—
4,0
4,2
4,4
—
—
—
—
—
3,6
3,6
3,8
3,8
—
—
—
—
3,0
3,2
3,2
3,4
3,4
—
—
—
3,0
3,0
3,2
3,2
3,4
3,4
—
—
3,0
3,0
3,0
3,2
3,2
3,4
3,4
—
2,5
2,5
2,5
3,0
3,0
3,0
3,2
3,2
7
Press cut diameter in aspiration-reducing film sheet