Pipe Design
TITANUS
SUPER·SENS
®
4 –
24
Data: 02/09
TSS_04_A-en-e
4.3.1.3 M-Pipe
system
TITANUS
®
d
TITANUS
®
A
B
C
D
Fig. 4.9: M-Pipe system for area protection
Limit values
Min. distance from TITANUS
®
to T-piece
4 m
Max. distance from TITANUS
®
to T-piece
20 m
Max. Branch length
50 m
Max. Overall pipe length per pipe system
150 m
Min. Distance between 2 aspiration apertures (d)
4 m
Max. Distance between 2 aspiration apertures (d)
12 m
Max. number of aspiration apertures (n) per pipe system
12 pcs.
Aspiration apertures
Number of apertures
per pipe system
3 6 9 12
Sampling aperture
∅
in
mm
9F
10
)
A
B
C
D
5,6
—
—
—
4,0
4,2
—
—
3,4
3,6
3,8
—
3,0
3,0
3,2
3,4
10
Press cut diameter in aspiration-reducing film sheet