TITANUS
SUPER·SENS
®
Pipe
Design
TSS_04_A-en-e
Data: 02/09
4 –
25
M-pipe system triggering thresholds
per pipe system
Number of apertures
3
6
9
12
1
blocked aperture
III
II
I —
10F
11
2
blocked apertures
{
11F
12
III
III
I
3
blocked apertures
{
III
III
III
4
blocked apertures
{
{
III
III
5
blocked apertures
{
{
{
III
6
blocked apertures
{
{
{
III
… has/have been detected at setting level x
Example
If blockage of 3 aspiration apertures of a total of 9 aspiration aper-
tures is intended to be detected, the air flow monitoring setting
switch should be set to level III.
Air flow monitoring level I, II or III should be set in any case for project
planning in conformity with EN 54-20.
11
— not possible
12
{
not purposeful
INSTRUCTION