Pipe Design
TITANUS
SUPER·SENS
®
4 –
28
Data: 02/09
TSS_04_A-en-e
4.3.2 Simplified pipe project planning
Simplified project planning is used for equipment protection and in rooms
with small dimensions. The advantage in this project planning is the uni-
form diameters of the aspiration apertures.
The specifications according to Chapter 4.2 apply to project planning.
The following limit values and aperture diameters should also be taken
into account. Additional accessories (air filters, condensation separators,
etc.) can influence the maximum pipe length.
4.3.2.1 I-pipe
system
TITANUS
®
TITANUS
®
d
Fig. 4.11: I-pipe system, such as for equipment protection
Limit values
Min. distance from TITANUS
®
to 1st sampling aperture
2 m
Max. distance from TITANUS
®
to 1st sampling aperture
10 m
Max. distance from the 1
st
sampling aperture to the last
sampling aperture
18 m
Max. overall pipe length Ø 25 mm
20 m
Max. number of aspiration apertures (n) per pipe system
10 pcs.
Minimum distance between aspiration apertures (d)
0,5 m
Maximum distance between aspiration apertures (d)
2 m
Aspiration apertures
Number of aper-
tures
2 3 4 5 6 7 8 9 10
∅
of all aspiration
apertures in mm
15F
16
)
6,0
5,0
4,4
4,0
3,6
3,6
3,6
3,4
3,4
16
Press cut diameter in aspiration-reducing film sheet