TITANUS
SUPER·SENS
®
Pipe
Design
TSS_04_A-en-e
Data: 02/09
4 –
31
4.3.2.4
Double U-pipe system
TITANUS
®
d
TITANUS
®
Fig. 4.14: Double U-pipe system, such as for equipment protection
Limit values
Min. distance from TITANUS
®
to 1st sampling aperture
2 m
Max. distance from TITANUS
®
to 1st sampling aperture
10 m
Max. distance from the 1
st
sampling aperture to the last
sampling aperture
5 m
Max. overall pipe length Ø 25 mm
20 m
Max. number of aspiration apertures (n) per pipe system
12 pcs.
Minimum distance between aspiration apertures (d)
0,5 m
Maximum distance between aspiration apertures (d)
2 m
Aspiration apertures
Number of apertures per pipe
system
4 8 12
∅
of all aspiration apertures in mm
18F
19
) 5,0
3,8
3,0
19
Press cut diameter in aspiration-reducing film sheet