4.3.4 Project planning for forced air flow
In case of project planning with forced air flow, please select the highest
alarm level according to the international specifications.
4.3.4.1
Detection of climatic cabinets with circulating air
Fig. 4.16: Air flow in climatic cabinets with circulating air (air circulator)
Due to the known flow conditions a simplified pipe installation is espe-
cially suitable for rooms which are ventilated by means of climatic cabi-
nets with circulating air.
The pipe system is to be installed outside of the pressure area as detection
in this area is not reliable due to high pressure and flow conditions!
The warmed up air in the room (e.g. caused by EDP-units) is aspirated
through openings in the ceiling void or directly through air inlets of a cli-
matic cabinet with circulating air. The air in the device is pressed by filter
elements, if necessary, cooled or warmed up and then blown into the
floor void of the room at the bottom side of the climatic cabinet. This
results in an „air circulator“ which circulates the whole air in the room.