Pipe Design
TITANUS
SUPER·SENS
®
4 –
34
Data: 02/09
TSS_04_A-en-e
Fig. 4.17: Monitoring possibilities of a climatic cabinet with circulating air
A room as illustrated in Fig. 4.17 is monitored by mounting a pipe system
at the
air inlet of the climatic cabinet with circulating air
(refer to
type 1).
It is possible to install the pipe system at the air outlet (in the floor void) if
no smoke particles are filtered in the climatic cabinet (refer to type 2).
In case of a detection through a pipe system before the air inlet or after
the air outlet of a climatic cabinet with circulating air it is important that
the room is not monitored if the climatic cabinet(s) is (are) not in opera-
tion.
ATTENTION