Installation
TITANUS
SUPER·SENS
®
5
– 6
Data:
02/09
TSS_05_A-en-e
5.3.1.6 Alarm
Thresholds
TITANUS
®
has three alarm thresholds, to which a defined bargraph-level
as threshold value belongs. The sensitivity at the smoke level display 10
depends on the chosen response sensitivity (refer to tables in chapter
5.3.1.4).
Alarm thresholds at the 4 sensitivity levels:
Alarm Level
Alarm threshold at …
fire alarm
100%
level 10
of the chosen response sensitiv-
ity
action alarm
70%
level 7
(=sensitivity at
alert alarm
35%
level 3,5
smoke level display 10)
After the action and the fire alarm thresholds have been reached it is al-
ways necessary to reset. The reset of the alarm is described in detail on
page 2.1.1 “Function“.
A reset option according to chapter 2.1.1 "Function" has to be installed!
5.3.1.7
Setting of the Ventilator Voltage
Fig. 5.3: Switching of the ventilator voltage on the base board
The standard setting of the ventilator voltage is 12 V. In critical areas the
ventilator voltage can be switched from 12 V to 15 V through closing the
bridge BR 6 in order to increase the transport speed in the pipe system
and to permit a quicker detection.
Re-initialize the air flow if you change the ventilator voltage. Close or
open the bridge only when the device is switched-off.
The bridge BR5 serves internal diagnostic purposes and has
always
to
be open.
INSTRUCTION
INSTRUCTION