2787-2147 (/0000-00x0)
Properties
Product manual | Version: 1.2.2
21
Power Supply Pro 2
!
NOTICE
Select conductor cross-sections according to current load!
In the event of a fault, the output current of a power supply can be up to 1.5 × I
OUT
. Only
use conductor cross-sections sufficient for the current load!
Table 21: Technical Data – Output Connection
Property
Value
Cross-section
Solid
0.50 … 10 mm² / 20 … 8 AWG
Fine-stranded
0.50 … 10 mm² / 20 … 8 AWG
Insulated ferrule with plastic collar
0.50 … 6.0 mm²
Ferrule without plastic collar
0.50 … 6.0 mm²
Strip length
13 … 15 mm / 0.51 … 0.59 inch
Specifications of the conductors used
≥ +75°C / +167°F (ambient air temperature: ≤
+60°C / 140°F)
≥ +90°C / 194°F (ambient air temperature: >
+60°C / 140°F)
Required tools (conductor termination)
Operating tool, with a partially insulated shaft,
type 3 (see section
8
3.9.4 Efficiency/Power Loss
Table 22: Technical Data – Efficiency/Power Loss
Property
Value
Efficiency, typ.
1)
110 VAC
93.9 %
230 VAC
95.4 %
Power loss, typ.
1)
110 VAC
30.4 W
230 VAC
23.3 W
1)
At nominal load