2787-2147 (/0000-00x0)
Properties
Product manual | Version: 1.2.2
27
Power Supply Pro 2
Standard
Title
Test
Value
Category
L+ → L−
0.5 kV
B
EN 61000-4-6
Part 4-6: Testing and measurement
techniques – Immunity to conducted
disturbances, induced by radio-fre-
quency fields
AC input
0.15 … 80 MHz:
10 V
A
DC output
0.15 … 80 MHz:
10 V
A
DC OK/
digital input/
digital output
0.15 … 80 MHz:
10 V
A
Communication
0.15 … 80 MHz:
10 V
A
EN 61000-4-8
Part 4-8: Testing and measurement
techniques – Power frequency mag-
netic field immunity test
50/60 Hz
30 A/m
A
EN 61000-4-11 Part 4-11: Testing and measurement
techniques – Voltage dips, short in-
terruptions and voltage variations im-
munity tests
40 % of 100 VAC (50
… 60 Hz)
5 cycles
C
70 % of 100 VAC (50
… 60 Hz)
0.5 cycles
B
0 % of 100 VAC (50
… 60 Hz)
250/300 cycles
C
Table 38: Legend for “Standards: EMC – Immunity to Interference (Tests Performed)”
Category
Description
A
Normal operation within specification limits
B
Temporary degradation of function that is self-recoverable after interference
C
Temporary loss of function that requires operator intervention or system reset
Table 39: Standards: EMC – Emission of Interference (Tests Performed)
Standard
Title
Test
Value
EN 55016-2-1
Part 2-1: Methods of measurement
of disturbances and immunity – Con-
ducted disturbance measurements
(CISPR 16-2-1)
Conducted distur-
bance
AC input
Class B (residential area) at nom-
inal load
EN 55016-2-3
Part 2-3: Methods of measurement
of disturbances and immunity – Ra-
diated disturbance measurements
(CISPR 16-2-3)
Housing interference
radiation
Class B (residential area) at nom-
inal load
EN 61000-3-2
Part 3-2: Limits – Limits for harmonic
current emissions (equipment input
current ≤ 16 A per phase)
Upper harmonic in-
put currents
Class A fulfilled at nominal load
3.10.4 Special Requirements
Observe the following:
• Perform installation according to the local conditions, applicable regulations (e.g., VDE
0100), national accident prevention specifications (e.g., UVV-VBG4 or DGUV Regula-
tion 2) and accepted technical regulations.
• This product is intended for installation in electrical systems or machines and fulfills the
requirements of the Low Voltage Directive.
When installing in machines, the following also applies:
• When installing in machines, normal operation must not commence until it is deter-
mined that the machine complies with the requirements of the Machinery Directive, EN
60204.