2787-2344 (/0000-00x0)
Notes on Operation
66
Product manual | Version: 1.0.1
Power Supply Pro 2
t
>110%
100%
20s
I
OUT
/ I
N
Figure 40: “Constant Current with Latching Shutdown” Mode
11.6.3 “Hiccup” Mode
In this mode, the output voltage is switched off if the nominal output current is exceeded
by a significant amount. After a few milliseconds, the output voltage is switched back on
to check whether the overload is still present. If the overload is still present, the output
voltage is switched back off. This process repeats until the overload has been eliminated.
t
100ms
500ms
>150%
100ms
100%
I
OUT
/ I
N
Figure 41: “Hiccup” Mode
11.6.4 “Electronic Circuit Breaker” Mode
In this mode, a specified trip current and trip delay can be set via the WAGO Interface
Configuration software or a connected
8
current exceeds the trip current setting, a specified amount of time elapses. If the output
current is still higher than the trip current setting after the trip delay corresponding to the
setting, the output is switched off. To switch the output back on, manual intervention is
necessary. The following options are available for this:
• Communication interface
• Buttons