10.3 PROFINET IO Diagnostics
PROFINET IO allows exact diagnostics of the type and source of an occurring
error by reading the record data sets for the diagnostics.
The respective configuration software / IO supervisor is normally used, which
provides graphical processing of the diagnostic data (e.g. STEP 7, etc.).
In addition to the record data sets for module/submodule parameterization, a
number of record data sets are available for acyclic communication for
diagnostics (listed in the following section).
The structure of the standardized diagnostic data sets and channel-specific
diagnostics are then explained.
Standard and manufacturer-specific diagnostic data sets are mapped according to
the extended channel diagnostics.
10.3.1 Diagnosis Data Sets
The diagnostic information of the fieldbus coupler (IO device) can be read
acyclically using standard diagnosis data sets (records). The structure of the data
sets is defined in the PROFINET IO specification.
More details are available in the specification under “IODReadReq” or
“IODReadRes”.
The data set number (index) makes it possible to distinguish between the
diagnostics level (device, module, submodule or channel error) and the
diagnostics structures.
The list of diagnosis data sets listed below provides the respective message
structures in the case of pending diagnostics.
Pos: 78 /Serie 750 ( WAGO-I/O-SYST EM)/Di agnose/Fel dbuskoppl er/-contr oller/PROF INET-Di agnose/PR OFIN ET IO-Diagnose - T eil 2 (370) @ 23\mod_1435733764818_21.docx @ 185034 @ @ 1
Table 64: Retrievable Record Data Sets for Diagnostics
Data set number
(index)
Description
Available on
slot
0x800A
32778 Standardized channel diagnostics of a submodule slot
(subslot specific)
0 … 128
0x800B
32779
0x800C
32780
0xC00A 49162 Channel diagnostics of a slot (slot specific); currently
identical with the data set number 800A, as only one
submodule can exist for each module.
0 … 128
0xC00B 49163
0xC00C 49164
0xE002
57346 Deviations in the specified and actual configuration of the
submodules assigned to the IO controller (IOAR).
0
0xE00A 57354 Channel diagnostics of all signal channels allocated to a
connection (AR), contains all channel diagnostics structures
of the submodule slots.
0
0xE00B
57355
0xE00C
57356
0xF00A
61450 Channel diagnostics of all signal channels allocated to the
application profile 0 (API 0), contains all channel
diagnostics structures of the individual submodule slots.
0
0xF00B
61451
0xF00C
61452