14.2.6 Analog Output Modules (AO)
All analog output modules receive a parameter data set from the IO controller in
the form of a record write request.
For standard modules, the parameter data set is sent to the data set number or
index 0x4000 or 16384.
This data set receives the following attributes.
Table 139: Parameterization – Overview of the Attributes for Analog Output Modules (AO)
Attributes for Analog Output Modules (AO)
-
Substitute value behavior of the outputs
-
Substitute output data
-
Process data format
Table 140: Parameterization AO – “Substitute Value Behavior” Attribute
Attribute name
Attribute value
Description
Substitute value
behavior of the outputs
If an established connection (AR) is disconnected
to which the submodule is assigned or when the
status of the “Provider State Flag” changes in the
APDU status of the consumer telegram from
“RUN” to “STOP”, the last valid status of the
respective output channel is retained for the
duration of the missing output data.
according to the
device settings
•
the parameterized substitute value behavior of
the station proxy is applied. The parameterized
substitute value of the respective output
channel has no meaning in this context.
Outputs are set to 0.
•
the data of all output channels is set to 0.
Outputs maintain the
last valid value.
•
the last valid status of the respective output
channel is maintained. The parameterized
substitute value of the respective output
channel has no meaning in this context.
Outputs take their
substitute values.
•
the parameterized substitute value of the
respective output channel is output..
Table 141: Parameterization AO – “Substitute Output Data” Attribute
Attribute name
Attribute value
Description
Substitute output data -32767 …
0
… 32767
In the state of missing output data, the set
substitute value is output on the respective output
channel with the set substitute value behavior
“Output substitute value”.
Table 142: Parameterization AO, DIA – “Process Data Format” Attribute
Attribute name
Attribute value
Description
Process data format
according to the
device settings
Station proxy (DAP) settings are applied.
INTEL (LSB-MSB) „Little Endian“ format
MOTOROLA
(MSB-LSB)
„Big Endian“ format“